VA-2 - Vacuum circuit breaker

Technical specifications

SPECIFICATIONS VA-2 / VA-2RP (12 - 17.5 - 24 kV) Unit 400A 630A 800A 1250A
Applicable standards
Rated voltage kV 12-17.5-24 12-17.5-24 12-17.5-24 12-17.5-24
Rated power frequence withstand voltage 1 min kV 28-38-50 28-38-50 28-38-50 28-38-50
Rated lightning impulse withstand voltage 1.2/50 µs kV 75-95-125 75-95-125 75-95-125 75-95-125
Rated frequence Hz 50/60 50/60 50/60 50/60
Rated current A 400 630 800 1250
Rated short time current kA 12.5-20-25 12.5-20-25 12.5-20-25 12.5-20-25
Rated duration of the short circuit s 3 3 3 3
Rated peak withstand current kA 31.5 - 50 - 63 31.5 - 50 - 63 31.5 - 50 - 63 31.5 - 50 - 63
Short circuit breaking current = Un kA 12.5 - 20 - 25 12.5 - 20 - 25 12.5 - 20 - 25 12.5 - 20 - 25
DC Component % 36 36 36 36
Short circuit making current kA 31.5 - 50 - 63 31.5 - 50 - 63 31.5 - 50 - 63 31.5 - 50 - 63
Rated operating sequence O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO O-0.3s-CO-15s-CO
Rated single capacitor bank breaking current at Un en fn = 50[Hz] A 400 400 400 400
Over voltage factor < 2.5 < 2.5 < 2.5 < 2.5
Rated breaking cable charging current A 25 25 25 25
Over voltage factor % < 4 < 4 < 4 < 4
Rated off load transformer breaking current A 12.5 12.5 12.5 12.5
Over voltage factor % < 4 < 4 < 4 < 4
Rated closing time ms 50 50 50 50
Rated opening time ms 42 42 42 42
Rated breaking time ms 60 60 60 60
Mechanical life time in number of CO operations 30.000 30.000 30.000 30.000
Life time of the vacuum interrupter years 30 30 30 30
Electrical life time of the vacuum interrupter cycles 10.000 10.000 10.000 10.000
Weight kg 118 121 121 124

xhtml - css / designed and developed by ITwebburo.be b.v.b.a. / © 2006 Deba nv / version 2.0.0 / privacy policy
Friday 30 July 2010