RV44 - Load-break switch

Technical specifications

Nominal voltage kV 12 17.5 24
Impulse withstand voltage 1,2/50 µsec
to earth and between phases kV 75 95 125
over the insulating distance kV 85 110 145
Power-frequency withstand voltage 1 min.
to earth and across phases kV 28 38 50
over the insulating distance kV 32 45 60
Rated frequency Hz 50/60 50/60 50/60
Nominal current1 A 800/1.250 800/1.250 800/1.250
Nominal short-time current 1sec. kA 25 25 20
Nominal rated peak value of the current kA 63 63 50
Breaking capacity RV44 (IEC 60265.1)
rated current A 800/1.250 800/1.250 630
closed loop A 800/1.250 800/1.250 630
load cable charging A 18 18 18
making capacity kA 63 63 50
earth fault A 100 100 100
earth fault cable charging A 30 30 30
internal arc 1 sec. (6 criteria) kA 16 16 16
Degree of protection IP4X
Mechanichal durability c/o 1000
Standards IEC 60298 Bijlage AA, IEC 60129, IEC 60420, IEC 60694, C 64-701 (only in Belgium), IEC 60265.1
Certificates KEMA

xhtml - css / designed and developed by ITwebburo.be b.v.b.a. / © 2006 Deba nv / version 2.0.0 / privacy policy