lida zayıflama hapı lida zayıflama hapı lida zayıflama hapı lida zayıflama hapı lida zayıflama hapı Deba nv: RV44 - Load-break switch: Drive mechanism

RV44 - Load-break switch: Drive mechanism

DA drive mechanisms

DA-M-Mec- DA-M-Mec -

In the case of DA drive mechanisms, the mechanism switches independently from the operator. The energy necessary for its operation is built up by compressing a spring. After a deadlock has been transgressed, this spring will perform the switch.

The spring compression can be achieved by manual operation (using the operating handle), or by motor operation (using either 24 V AC/DC, 48 V AC/DC, 110 V AC/DC or 220 V AC/DC).

Any motor-operated drive mechanisms may, at any time, be operated manually as well. To achieve this, the operating handle is placed on the operating shaft of the RV44 load-break switch, after which a slight pressure is applied to the handle in order to release the connection between the operating shaft and the motor.

drive mechanisme function load-break switch function earthing switch manual operation motor operation
DA-MEC X X x -
DA-M-MEC X X X* X
DA-K-MEC X - X -
DA-K-M-MEC X - X* X
DA-EDN-D-MEC X X X -
* in case of any defects

designed and developed by ITWEBOFFICE / © 2009 Deba nv / version 2.0 / privacy policy
 08  2012
Important alert!
  • Deze webbrowser biedt te weinig ondersteuning voor deze website. Lees hier meer.