RV44 - Load-break switch

Certificates

Test Specification Test results
Insulating level IEC 60265.1
IEC 60298
IEC 60694
Power-frequency withstand voltage 1 min.
  • to earth and between phases: 38 kV
  • over the insulating distance: 45 kV
Lightning-impulse withstand voltage 1.2/50 µsec
15 positive and 15 negative impulses per phase
  • to earth and between phases: 95 kV
  • over the insulating distance: 110 kV
Rated making and breaking capacity IEC 60129
IEC 60265.1
Component Temperature rise
Allowed Measured
Pole terminals 65 °C 47,5 °C
Bus bar 65 °C 59 °C
IEC 60265.1 Nominal current 800 A
Short-time current 25 kA / 1 sec.
IEC 60265.1
Class E3
Number of switching Type of switching: Current (Ampere): Cos
Function 1 (100 %) 100 C(O) 800 0,7
Function 2 (5 % In) 20 C(O) 42 0,7
Function 2a 20 C(O) 800 0,7
Function 4a (100 %) 10 C(O) 5 Cap
Function 4a (30 %) 10 C(O) 5 Cap
Function 5 5 C 63000 0,7
Function 6a 10 C(O) 100 0,7
Function 6b 10 C(O) 30 0,7
Mechanical endurance test IEC 60265.1
IEC 60298
1000 operations