DR-6 - Ring Main Unit

Technical specifications

Rated voltage kV 12 17,5 24
General specifications
Impulse withstand voltage 1,2/50 µsec
To earth and between phases kV 75 95 125
Over the insulation distance kV 85 110 45
Power frequency voltage test 1 min.
To earth and between phases kV 28 38 50
Over the insulation distance kV 32 45 60
Rated frequency Hz 50/60
Rated current A 630 400/630
Rated short time current 1 sec kA 25 20 12,5/16/20
Rated peak value of the current kA 63 50 40/50
Breaking capacity (IEC 60265.1) ClassE3
Rated current A 630 630 400/630
Closed loop A 630 630 400/630
No load cable A 30 30 30
Earth leakage fault A 100 100 100
Line feeder
Rated current A 630 630 630
Rated short time current 1 sec kA 25 20 12,5/16/20
Rated peak value of the current kA 63 50 1,5/40/50
Transformer feederl
Rated current A 200 200 200
Fuse switch
Short circuit breaking capacity (limited by the fuse) kA 25 25 16/20
making capacity kA 63 63 40/50
Circuit breaker
Short circuit breaking capacity 1 sec. kA 25 20 20
Making capacity kA 63 50 50
Internal arc 1 sec IEC 60298 - 6 criteria kA 16 16 16
Degree of protection IP7x
Rated gas pressure at 20 °C Bar 0,3 bar overpressure

More data :