| Rated voltage |
12 |
17,5 |
24 |
| Impulse withstand voltage 1,2/50 µsec |
|
|
|
| To earth and between phases |
75 |
95 |
125 |
| Over the insulation distance |
85 |
110 |
45 |
| Power frequency voltage test 1 min. |
|
|
|
| To earth and between phases |
28 |
38 |
50 |
| Over the insulation distance |
32 |
45 |
60 |
| Rated frequency |
50/60 |
| Rated current |
630 |
400/630 |
| Rated short time current 1 sec |
25 |
20 |
12,5/16/20 |
| Rated peak value of the current |
63 |
50 |
40/50 |
| Breaking capacity (IEC 60265.1) |
ClassE3 |
| Rated current |
630 |
630 |
400/630 |
| Closed loop |
630 |
630 |
400/630 |
| No load cable |
30 |
30 |
30 |
| Earth leakage fault |
100 |
100 |
100 |
| Rated current |
630 |
630 |
630 |
| Rated short time current 1 sec |
25 |
20 |
12,5/16/20 |
| Rated peak value of the current |
63 |
50 |
1,5/40/50 |
| Rated current |
200 |
200 |
200 |
| Short circuit breaking capacity (limited by the fuse) |
25 |
25 |
16/20 |
| making capacity |
63 |
63 |
40/50 |
| Short circuit breaking capacity 1 sec. |
25 |
20 |
20 |
| Making capacity |
63 |
50 |
50 |
| Internal arc 1 sec IEC 60298 - 6 criteria |
16 |
16 |
16 |
| Degree of protection |
IP7x |
| Rated gas pressure at 20 °C |
0,3 bar overpressure |