DF-2 - Medium voltage switchgear

Technical specifications

Rated voltage kV 12 17,5 24
Impulse withstand voltage 1.2 / 50 µs
- to earth and between phases kV 75 95 125
- over the insulating distance kV 85 110 145
Power-frequency withstand voltage 1 min.
- to earth and between phases kV 28 38 50
- over the insulating distance kV 32 45 60
Rated frequency Hz 50/60 50/60 50/60
Rated current 1 A 800/1.250 800/1.250 800/1.250
Rated short circuit time current 1s. kA 25 25 20
Rated peak value of the current kA 63 63 50
Breaking capacity RV44 (IEC 60265.1)
- rated current A 800/1.250 800/1.250 630
- closed loop A 800/1.250 800/1.250 630
- load cable charging A 18 18 18
- making current kA 63 63 50
- earth fault A 100 100 100
- earth fault cable charging A 30 30 30
- internal arc 1 sec. (6 criteria) kA 16 16 16
Degree of protection IP4X
Mechanichal durability c/o 1000
Standards IEC 62271-100, IEC 62271-102, IEC 62271-105, IEC 62271-200, IEC 60129, IEC 60694, C 64-701 (only in Belgium) IEC 60265.1
Certificates 630
1 In conformity with IEC 60265.1, class E3.

Types

xhtml - css / designed and developed by ITwebburo.be b.v.b.a. / © 2006 Deba nv / version 2.0.0 / privacy policy
Friday 30 July 2010