Deba nv recommendations concerning the installation room The safety of the system is determined by more factors than the intrinsic safety of the construction in itself.
Therefore, Deba nv operates a number of installation directions in its technical documentation. These directions are subdivided in recommendations concerning:
| description | value |
| Ambient temperature | min. -15 °C / max +45 °C |
| Relative air humidity | min. 10 % / max. 70 % (without the formation of condensation) |
| Installation altitude | max. 1000 m above sea level |
Contact Deba nv when cubicles must be installed in areas where the surrounding conditions cannot be guaranteed.
| transformer capacity (in KVA) | P tot (W) |
| 100 | 1.605 |
| 160 | 2.175 |
| 250 | 2.850 |
| 315 | 3.412 |
| 400 | 4.012 |
| 500 | 4.837 |
| 630 | 5.745 |
| 800 | 6.787 |
| 1.000 | 7.875 |
| 1.250 | 10.350 |
| 1.600 | 12.450 |
| 2.000 | 16.125 |
The free space above the construction must be at least 2,200 mm. Depending on the Utility, an even larger minimum space may be required. An ideal - and accepted by all Utilities - amount of free space is 2,500 mm.
With cast resin transformers with a power of >= 1,250 KVA, the free height must be at least 2,500 mm.
The dimensions given apply for all doors accessing the installation area. These minimum door sizes therefore also apply when the installation area is not directly accessible from the outside.
| omschrijving | waarde |
| Height of the entrance door | min. 2.200 mm |
| Width of the entrance door | min. 100 mm + width of the widest cell |
If the medium voltage switchgear does not contain transformer cubicle(s), a minimum door height of 2,000 mm will be sufficient.
If a transformer is included, refer to the transformer dimensions. For the correct dimensions of the various cubicles, see "Dimensions and weights".
If the medium voltage switchgear must be installed in basements or storage basements, an entrance hatch must be supplied which length as well as its width is at least 400 mm larger than the dimensions of the largest cubicle or the transformer.
The free passage in front of the cubicles depends on the composition of the medium-voltage switchgear.
If the medium-voltage switchgear does not contain transformer housings, the minimum free passage is 1,500 mm. The preferable amount of free passage is 2,500 mm. In the case of medium-voltage switchgear with a transformer housing, with a power of >= 1.000 KVA the free passage has to be minimum of 2,000 mm.
To prevent major material damage and serious physical injury or electrocution in the (unlikely) event of an internal arc, the following installation instructions apply:
In medium voltage switchgears installed in accordance with the above-described installation procedure, the (unlikely) event of internal arc will always be restricted to the compartment in which it occurred.